574-771Rev. A4020 Fire Alarm SystemSystem Troubleshooting GuideTechnical Manuals Online! - http://www.tech-man.com
2-5KEYPAD/LEDsLCD DISPLAYMASTER CONTROLLER(565-325)P1P8P2STANDARD SLAVE(565-222)POWER I/O INTERFACE(565-220)POWER SUPPLY(636-289)P3TB1TO PROGRAMMER CA
2-6Figure 2-3. 565-325 Master Controller PCB AssemblyTable 2-2 describes the I/O connectors on the Master Controller PCB Assembly(refer to Figure 2-2
2-7The Standard Slave PCB assembly controls and supervises four I/O circuits, asingle Mapnet channel and the Power I/O Interface assembly and has thef
2-8Figure 2-4. 565-222 & 565-368 Standard Slave PCB AssemblyTable 2-4 describes the I/O connectors on the Standard Slave PCB Assembly(refer to Fig
2-9The Power I/O Interface circuitry permits the Standard Slave to supervise andcontrol the Power Supply. A bi-directional 8 bit bus provides Standar
2-10Figure 2-5. 565-256 Power I/O Interface PCB AssemblyFigure 2-6. 565-220 Power I/O Interface PCB AssemblyFigure 2-7. Voltage Points on Power I/O
2-11Table 2-5 describes the I/O connectors on the 565-256 Power I/O Interface PCBAssembly (refer to Figure 2-5 for the location of these connectors).T
2-12The Switcher Power Supply converts 120/220/240VAC input line voltage into28 volt DC power. The supply provides brownout detection status to the P
3-1This chapter presents 4020 problems experienced in the field and those analyzedby Service Repair. This information is arranged in three categories
3-2Removing the AC power cable connection from the Power Supply still leavesprimary AC power on the terminal block to the right of the supply. During
Copyright 1998 Simplex Time Recorder Co. All rights reserved.Printed in the United States of America.Information in this document is subject to cha
3-3Two Standard Slave PCB assembly versions exist. Although the assembliesappear to be identical, each assembly requires specific Software, Power I/O
3-4Some back boxes have a conduit fitting mounted in the upper right-hand cornerwhere it is possible to contact the rear of the P3 connector of the LC
3-5Multiple ground faults and mis-application of the Audible/Visible jumpers candestroy the 10 ohm protective resistors (R35, R63, R70 and R77) on the
3-6Although the Power Supply exhibits the least failures of all 4020 sub-assemblies, many power supplies are being damaged by reversal of the batteryl
4-1Generally speaking, the first step in troubleshooting is to determine what thecustomer knows about the problem. For example:• Was panel alarm sou
4-2The typical selections on a Power I/O Interface PCB assembly are as follows:Power I/O Interface Board 565-256:• P10, P11, P12, P14 installed to e
4-3If the Master Controller comes up with a “System Startup in Progress” message,it is probably working properly. Error codes are usually an indicati
4-4A non-silenceable panel alarm usually means that the Master Controller does nothave +28V power. +28V originates from the Power I/O InterfaceUninte
4-5The measured voltage at the B-tap output terminals on the Power I/O Interfaceboard should be 28.5V ±.2V. If the B-tap is not the correct voltage th
4-6No 36V Mapnet output indicates the Standard Slave is not completing the powerinitialization procedure. It could be unable to access the A/D conver
iTables and Figures In this Document... iiChapter 1 About This DocumentIntroduction ...
4-7Table 4-1 shows several indications of problems with potential causes associatedwith each.Table 4-1. Troubleshooting ChartIndication of Problem Ar
4-8Table 4-1. Troubleshooting Chart (continued)Indication of Problem Areas to CheckIf panel alarm is sounding continuouslywith no relays clickingChec
5-1The following sequence is documented FOR REFERENCE ONLY.On start-up, the 4020 Standard Slave Card performs the checks shown in Table 5-1.Table 5-1.
5-2Table 5-1. Standard Slave Initialization Sequence (continued)Card Operation Remarks19. Turn on taps If there is 28.5V at the A & B Taps, 27.6V
Rev. ASimplex Time Recorder Co. Simplex Plaza Gardner, Massachusetts 01441-0001 U.S.A.574-771Technical Manuals Online! - http://www.tech-m
iiTables and Figures in this DocumentTables Table Description PageTable 2-1 4020 System Device Address Assignments 2-2Table 2-2 565-325 Master Control
1-1This troubleshooting guide provides you with a basic understanding of the 4020Fire Alarm Control Panel operation and suggestions for quickly findin
2-1The basic 4020 Fire Alarm Control Panel is comprised of four assemblies:• Master Controller (Part No. 565-325)• Standard Slave (Part No. 565-368
2-2The basic 4020 Fire Alarm Control Panel is capable of supporting systemexpansion with peripheral cards. Although not discussed further in thistrou
2-3The Master Controller PCB assembly supervises panel operations and controlsthe front panel user interface. The Master Controller communicates with
2-4KEYPAD/LEDsLCD DISPLAYMASTER CONTROLLER(565-325)P1P8P2STANDARD SLAVE(565-368)POWER I/O INTERFACE(565-256)POWER SUPPLY(636-341)P3TB1TO PROGRAMMER CA
Kommentare zu diesen Handbüchern